Functions
and characteristics
Switch set to the “Auto” position (automatic operation and test mode).
DB101598
WAITING The system exits this mode when the
operating mode is modied or when an
external event occurs (e.g. failure or return
of UN).
When the UA controller is not energised, the output for
generator set startup is activated).
Key
UN : “Normal” source voltage
UR : “Replacement” source voltage
N : “Normal” source circuit breaker
R : “Replacement” source circuit breaker
B : Penalties accepted (N ON), i.e. B = 1
(*) The test lasts 180 seconds.
1
The number sends to the indicated step when
the condition is true.
Associated controllers
UA controller
Operating sequences
Livre 1.indb 25 08/10/2008 18:39:06